Back
Protection 24.02.2026 · 9 min read

Choosing the Right Circuit Breaker (MCB)

Circuit Breaker MCB Characteristic Overcurrent Protection

The Miniature Circuit Breaker (MCB) is the central protection device in every electrical installation. It protects cables from overload and short circuit and is mandatory in every circuit. Selecting the correct trip characteristic and rated current is essential for a safe and functional installation.

Important to Know

An MCB primarily protects the cable – not the connected device or the person. For personal protection, an additional RCD (Residual Current Device) is required.

What is a Miniature Circuit Breaker?

A Miniature Circuit Breaker (MCB) is a thermo-magnetic protective switch. It combines two tripping mechanisms in one device.

The thermal release (bimetal) responds to slow overload, while the magnetic release (coil) trips instantly on short circuit. This reliably protects the cable in both fault scenarios.

Trip Characteristics Comparison

The trip characteristic determines at what multiple of the rated current the magnetic instantaneous release trips. Different types are needed depending on the application.

Characteristic B

Magnetic tripping: 3 to 5 times rated current

Standard application in residential and office buildings. Suitable for resistive loads such as lighting, sockets and heaters.

Characteristic C

Magnetic tripping: 5 to 10 times rated current

For loads with moderate inrush currents such as motors, fluorescent lamps, air conditioning units and transformers.

Characteristic D

Magnetic tripping: 10 to 20 times rated current

For loads with high inrush currents such as large motors, welding machines, X-ray equipment and UPS systems.

Characteristic K

Magnetic tripping: 8 to 14 times rated current

Special application for transformers and motors with particularly high starting currents in industrial environments.

Rated Currents and Cable Assignment

The rated current of the MCB must match the current carrying capacity of the connected cable. Here are the most common assignments for copper cables installed in conduit:

Rated Current Typical Use Min. Cable Size (Cu)
6 A LED lighting circuits 1,5 mm²
10 A Lighting, lightly loaded socket circuits 1,5 mm²
13 A Socket circuits (UK/IE standard) 1,5 mm²
16 A Socket circuits (DE standard), individual appliances 2,5 mm²
20 A Instantaneous water heater (single-phase), wallbox 2,5 mm²
32 A Cooker, instantaneous water heater (three-phase), 22kW wallbox 6 mm²

Selectivity and Back-Up Protection

Selectivity means that in the event of a fault, only the nearest protective device trips rather than shutting down the entire installation. This is particularly important for supply reliability.

Selectivity Tips

  • The upstream MCB should have at least 1.6 times the rated current of the downstream one
  • Refer to manufacturer selectivity tables – not all combinations are selective
  • When in doubt, use selective main circuit breakers (SLS) as upstream protection

Working Together with RCDs

In modern electrical installations, MCBs are always used in combination with RCDs (Residual Current Devices). Proper coordination of both devices is important.

Best Practices

  • Always install the RCD upstream of the MCBs (in the energy flow direction)
  • Rated current of the RCD should be equal to or greater than the sum of downstream MCBs (considering diversity factor)
  • Maximum 6 MCBs per RCD for optimal selectivity and availability