Thoughtful placement of sockets and switches prevents power strips, loose cables and later rework.
This guide shows standard mounting heights, sensible distances and concrete recommendations per room – practical and aligned with standards.
Defines, among other things, the minimum number and arrangement of sockets per room (equipment classes).
Regulates installation zones and cable routing in walls and ceilings.
Electrical safety, protective measures and residual current protection.
The following recommendations do not replace professional planning. Always observe the applicable standards and have the installation carried out by qualified electricians.
Element | Standard | Accessible |
---|---|---|
Sockets (general) | 30-40 cm | 40-85 cm |
Sockets kitchen work area | 100-120 cm | 85-105 cm |
Light switch | 105-110 cm | 85 cm |
TV/Multimedia outlets | 30 cm | 40-85 cm |
LAN outlets | 30 cm | 40-85 cm |
Tip: Plan a media‑wall panel with flush outlets (230V, LAN, SAT, HDMI) behind the TV.
Note: Check load distribution and use separate circuits for work appliances.
Protection zones according to DIN VDE 0100‑701 (example)
Zone | Area | Installation |
---|---|---|
0 | Inside tub/shower | Only SELV equipment, no sockets |
1 | Up to 2.25 m above tub/shower | Fixed devices with suitable IP rating, no sockets |
2 | 60 cm around zone 1 | Luminaires IPx4, sockets only outside zone 2 |
3 | Outside the zones | Normal sockets with RCD permitted |
Tip: Plan double socket inserts at each bedside (charging + lamp).
Tip: A central tech/network cabinet creates order and reserves.
Check needs per room: usage, furniture, media zones.
Observe standard heights and distances.
Dimension sufficient circuits, RCDs and cross‑sections.
Provide reserves and blank boxes.
Plan special outlets (LAN, SAT, USB, KNX).
Reconcile documentation and plan status.
With forward‑looking planning you avoid power strips and create comfort – today and in the future.