The VDE-AR-N 4100 replaced the old TAB recommendations in 2019 and applies nationwide. It regulates meter cabinet, main line and registration of consumers and generators. This overview shows what has specifically changed for electricians and homeowners.
From house connection to registration — the application rule covers the entire interface between grid and house installation.
Connection capacity, house service box, cable entry.
Layout, minimum dimensions, reserve positions, eHZ integration.
Wallbox, heat pump, AC, sauna from certain capacity.
PV, CHP, battery storage — registration also per VDE-AR-N 4105.
Future connection point: an additional reserve position with fixed size for future expansion such as wallbox or PV converter.
The meter cabinet for a single-family home must be at least 1.10 m wide. Smaller cabinets are rejected by the grid operator.
Pluggable meters with eHZ adapter are the rule today. Components such as load-break terminals are required.
Preparation for Smart Meter Gateway (SMGW) in the meter location — even if no smart metering system is currently installed.
Electricians and homeowners must know these dimensions.
| Parameter | Minimum | Note |
|---|---|---|
| Minimum width SFH | 1.10 m | 3-field cabinet |
| Inner height | 1,050 mm | Installation height |
| Reserve fields | ≥ 1 field | For future consumers |
| APZ | Mandatory | Future connection point |
| SMGW space | prepared | Gateway preparation |
These limits decide whether a consumer or generator only needs to be reported or requires formal approval.
Up to 11 kW notification-required, from 12 kW approval-required.
Notification to grid operator. For controllable consumers (§14a EnWG) additional requirements.
Up to 30 kWp usually notification-required. Registration via VDE-AR-N 4105.
Registration required per VDE-AR-N 4105. Larger storage requires formal approval.
Generous reserve positions
Always plan 1-2 additional reserve fields. Wallbox and PV often come years later.
Position APZ correctly
The APZ must be accessible from above and must not be blocked. Document the position clearly.
Early coordination
Some grid operators have additional requirements beyond VDE-AR-N 4100. Ask the grid operator before purchasing the cabinet.
VDE-AR-N 4100 brings nationwide uniformity — good for planners. Still, there are local variations. Anyone planning with a large cabinet plus APZ is on the safe side everywhere.
💡 Tip: Download VDE-AR-N 4100 in its original wording — online summaries often omit critical details.
myElectricPlan supports VDE-AR-N 4100 directly in the switchgear editor: APZ, reserve fields and SMGW preparation are accounted for automatically.
Plan VDE-AR-N 4100 compliant now