Always choose a cable cross-section with at least 20% reserve above the calculated load to allow for future expansions and avoid overloads.
The voltage drop should not exceed the following values:
Always observe applicable standards (VDE 0100, DIN 18015) and have electrical installations carried out by professionals. The calculator is for guidance only.
This setting is used for all calculations
The calculator takes into account both voltage drop and current carrying capacity and chooses the greater of the two values as the recommended cable cross-section.
Cross-section (mm²) | Current carrying capacity (A) |
---|
* Values apply to copper conductors at 30°C ambient temperature
* Installation: B1 (in electrical installation conduit on or in the wall)
Cross-section (mm²) | Current carrying capacity (A) |
---|
* Values apply to copper conductors at 30°C ambient temperature
* Installation: B2 (multi-core cable in electrical installation conduit)
The values given in the tables apply to standardized installation methods. Depending on the specific installation, correction factors may be necessary:
Important: In case of doubt, always consult a qualified electrician!